Electrical Specifications |
|
|
AC Input Voltage |
|
120 VAC |
|
|
AC Input Low Transfer Voltage |
|
40-105 VAC |
|
|
AC Input Current |
|
55 amps AC - 30 amps AC pass through and 25 amps AC charging |
|
|
Continuous Power (@ 25 °C) |
|
1500 VA |
|
|
Efficiency (peak) |
|
94% |
|
|
Output Voltage (RMS) |
|
120 VAC |
|
|
Maximum Output Voltage Regulation |
|
+/- 5% |
|
|
Frequency (nominal) |
|
60 Hz |
|
|
Continous Output (@ 25°C) |
|
12.5 amps AC |
|
|
5 Sec Rating Surge Capability |
|
2400 watts |
|
|
1 mSec Surge Capability |
|
38 amps AC |
|
|
100 mSec Surge Capability |
|
27 amps AC |
|
|
Automatic Transfer Relay |
|
30 amps |
|
|
DC Input Voltage (nominal) |
|
12.6 VDC |
|
|
DC Input Voltage Range |
|
10.8-15.5 VDC |
|
|
DC Current at Rated Power |
|
165 amps DC |
|
|
Short circuit current |
|
400 amps DC |
|
|
Idle Consumption (typical at full voltage) |
|
<9 watts |
|
|
Search Mode Consumption |
|
< 1 watt |
|
|
Low Battery Protection (enabled) |
|
11 VDC |
|
|
Maximum Charge Rate (adjustable) |
|
70 amps DC |
|
|
Waveform |
|
Modified Sine Wave |
|
|
Load Sensing (inverter mode) |
|
Adjustable 5 to over 100 watts |
|
|
General Specifications |
|
|
Specified Temperature Range |
|
32 °F to 104 °F (0 °C to 40 °C) |
|
|
Enclosure Type |
|
Indoor, ventilated, steel chassis with powder coat finish |
|
|
Unit Weight |
|
35 lb (16 kg) |
|
|
Shipping |
|
39 lb (18 kg) |
|
|
Dimensions (H x W x D) |
|
8.5 x 22 x 7.25" (21.6 x 55.9 x 18.4 cm) |
|
|
Shipping Dimensions (H x W x D) |
|
13 x 25 x 12" (33 x 63.5 x 18.4 cm) |
|
|
Mounting |
|
Horizontal wall mount |
|
|
Warranty |
|
2 years |
|
|
Part Numbers |